The challenge: precise temperature control for MHRA-compliant storage
Kent Pharmaceuticals, a family business established in the early 1980s, has grown to become Britain's largest independent generic pharmaceuticals manufacturer and leading wholesaler. JET was approached to provide a temperature control solution at the company's new warehousing facility in Measham — two units with a combined floor space of 90,000 sq ft — where internal conditions had to satisfy MHRA guidelines for the storage of pharmaceutical products.
- Internal operating temperature had to be held between 18°C and 25°C throughout, in line with MHRA guidance
- Two separate warehouse units, totalling 90,000 sq ft, both required conditioning
- Extensive roof lights created a risk of excessive solar heat build-up within the space
- A robust monitoring regime was needed to evidence ongoing compliance to auditors and customers
Our solution: a single JET Air Induction System for each warehouse
Given the scale of the buildings, JET specified a single Air Induction System for each unit, combining gas-fired heating with DX cooling — both readily available on site — to hold the required temperature range year-round.
- Air handling units mounted externally at ground level in both units, saving valuable internal floor space
- Plant sized against external summer design conditions of 32°C DB / 21°C WB, to hold performance even in extreme weather
- Solar protection recommended for the roof lights, cutting heat gain and allowing smaller AHUs and condensing units to be specified
- 14 temperature sensors installed across both sites (8 in the larger unit, 6 in the smaller) — well beyond the usual four — feeding a continuous monitoring and recording system
What we delivered
MHRA-compliant conditions
Maintains a steady 18°C–25°C across both warehouses, satisfying MHRA guidelines for pharmaceutical storage.
90,000 sq ft, one system per unit
A single JET Air Induction System conditions each warehouse, with externally mounted AHUs freeing up internal floor space.
14-point temperature monitoring
Far exceeding the usual four-sensor setup, a dedicated network provides continuous monitoring and recording across both sites.
Delivered on schedule
Both installations were completed on time and, in Kent's own words, "trouble free."
What the client said
"On taking on both warehouses, we had the opportunity to address our temperature control requirements and JET responded quickly. They were meticulous in their planning and both installations were trouble free. We routinely show off the air induction systems to our customers, which not only is great PR for Kent, but also shows that we are committed to MHRA guidelines and ultimately, patient safety."
Jason Atkins, Facilities Manager, Kent Pharmaceuticals – Measham
Inside the installation
Show technical specifications
| Location | Measham, Leicestershire |
|---|---|
| Facility type | Two new warehouse units |
| Floor area | 90,000 sq ft (combined) |
| Regulatory standard | MHRA guidelines (pharmaceutical storage) |
| Heating | Gas-fired |
|---|---|
| Cooling | DX (direct expansion) |
| AHU mounting | External, ground level (1 per unit) |
| Temperature range | 18°C – 25°C |
| External design conditions | 32°C DB / 21°C WB |
| Monitoring | 14 sensors (8 + 6), continuous recording |
From frost protection to multi-zone climate control, our engineers design bespoke HVAC systems that perform. If you have a facility with a similar problem, talk to us about it.